Parameters
Parameter used
Parameter 22-80 Flow Compensation
Parameter 22-81 Square-linear Curve Approximation
Parameter 22-82 Work Point Calculation
Parameter 22-83 Speed at No-Flow [RPM]/parameter 22-84 Speed at No-
Flow [Hz]
Parameter 22-85 Speed at Design Point [RPM]/parameter 22-86 Speed at
Design Point [Hz]
Parameter 22-87 Pressure at No-Flow Speed
Parameter 22-88 Pressure at Rated Speed
Parameter 22-89 Flow at Design Point
Parameter 22-90 Flow at Rated Speed
Table 4.14 Speed at Design Point Known/Unknown
22-80 Flow Compensation
Option:
Function:
[0]
Disabled Setpoint compensation not active.
*
[1]
Enabled Setpoint compensation is active. Enabling this
parameter allows the flow-compensated setpoint
operation.
22-81 Square-linear Curve Approximation
Range:
Function:
NOTICE
100 %
[0 - 100 %]
*
Not visible when running in cascade.
Example 1
Adjustment of this parameter allows the
shape of the control curve to be adjusted.
0=Linear
100%=Ideal shape (theoretical).
H
(head)
Control Curve
Illustration 4.21 Square-Linear Curve Approximation
MG03N202
Programming Guide
Speed at design point
22-82 Work Point Calculation
Option:
Q
( ow)
Danfoss A/S © 11/2015 All rights reserved.
Speed at design point
KNOWN
UNKNOWN
+
+
+
+
+
+
-
-
-
Function:
Example 1
H
(head)
H
A
DESIGN
Set Point
H
MIN
Par.:
22-83/
Control Curve
22-84/
22-87
Q
Illustration 4.22 Speed at System Design
Working Point is Known
From the datasheet showing characteristics for the
specific equipment at different speeds, simply
reading across from the H
DESIGN
Q
point allows finding point A, which is the
DESIGN
system design working point. The pump character-
istics at this point should be identified and the
associated speed programmed. Closing the valves
and adjusting the speed until H
achieved allows the speed at the no-flow point to
be identified.
Adjustment of parameter 22-81 Square-linear Curve
Approximation then allows the shape of the
control curve to be adjusted infinitely.
Example 2
Speed at system design working point is not
known: Where the speed at system design
working point is unknown, another reference point
on the control curve needs to be determined
based on the datasheet. By looking at the curve
for the rated speed and plotting the design
pressure (H
, Point C), the flow at that
DESIGN
pressure, Q
, can be determined. Similarly, by
RATED
plotting the design flow (Q
DESIGN
+
+
+
+
-
4
+
+
+
+
(flow)
point and the
has been
MIN
, Point D), the
111
4

Advertisement