4.1.1
Display Port
Before shipment, the display port has been connected to the 10" touch panel with the
designated cable in Delta factory.
4.1.2
REPO Dry Contacts
Connect the REPO dry contacts to a user-supplied switch and you can remotely shut down
the UPS when an emergency occurs. The REPO dry contacts provide normally open (NO)
and normally closed (NC) these two options for use.
NOTE:
To enable the normally closed (NC) function, please take out the dry contact card
and remove its Jump CNR3 before you turn on the UPS.
(Figure 4-2: REPO Dry Contacts & Schematic)
(Figure 4-3: Location of the Dry Contact Card)