4.2 Messages after a data transfer with a DX-COM-STICK2

4.3 Operating status indicators

Message
Possible causes and fixes
The analog input's input current does not fall within the specified range.
4-20 F
• Check the setting in P-16 for AI1 and P-47 for AI2
In the case of 4-20mA:
• Check the setpoint connection for wire breakage
Internal error
SC-FLt
• Please contact your nearest Eaton sales branch
Internal error
FAVLty
• Please contact your nearest Eaton sales branch
Table 23: Possible messages after a data transfer
View
Description
Parameter transfer to DX-COM-STICK2 was successful
PASS-r
DX-COM-STICK2 locked.
OS-Loc
In order to transfer data, check the switch position on the side.
Error while attempting to read the parameters from the variable frequency drive.
FAiL-r
Parameter transfer to variable frequency drive successful.
PASS-t
The parameter set stored in the DX-COM-STICK2 is for a different rating (different motor
FAiL-P
current, motor output, etc.) than that of the connected variable frequency drive.
Error when attempting to copy parameter set to variable frequency drive
Fail-t
No data found in DX-COM-STICK2.
no-dAt
Parameter set in variable frequency drive locked. Unlock variable frequency drive first.
dr-Loc
The variable frequency drive has an enable signal and cannot take new parameters.
dr-rVn
Stop the variable frequency drive.
The parameter set stored in the DX-COM-STICK2 does not match the variable frequency drive.
tyPE-E
Only transfers from the variable frequency drive to the DX-COM-STICK2 are possible.
The DX-COM-STICK2 is not compatible with the variable frequency drive.
tyPE-F
The six flashing dots on the seven-segment display are used to indicate
various operating statuses.
8 . 8 . 8 . 8 . 8 . 8 .
1
2
3
4
5
6
Number(s)
Behavior
1, 2, 3, 4, 5, 6
Flash synchronously
1, 6
Flash in an alternating
pattern
1
Flashes
DC1...E1 Variable Frequency Drives 11/16 MN040022EN www.eaton.com
4.2 Messages after a data transfer with a DX-COM-STICK2
Significance
Overload
The current current exceeds the value set with P-08.
Power outage or power supply switched off
Fire Mode enabled
4 Messages