Fault Code; Monitoring Data - Eaton SV9000 Applications Manual

Af drives-motor pump enhanced protection application
Hide thumbs Also See for SV9000:
Table of Contents

Advertisement

Page 52 (60)

7 Fault Code

The Motor Pump Enhanced Protection application has some extra fault codes:
Fault Number
Fault
27
Fieldbus
communication error
50
Hot Motor Winding
51
Hot Motor Bearing
52
Seal Leak Detection
53
High Vibration

8 Monitoring Data

The Multipurpose Application II has extra items for monitoring (n21 - n22). See table 8-1.
Data
Data Name
Number
V1
Output frequency
V2
Motor speed
V3
Motor current
V4
Motor torque
V5
Motor power
V6
Motor voltage
V7
DC-link voltage
V8
Temperature
V9
Operating day counter
V10
Operating hours "trip counter"
V11
MW-hours
V12
MW-hours, "trip counter"
V13
Voltage/analog input
V14
Current/analog input
V15
Digital input status, gr. A
V16
Digital input status, gr. B
V17
Digital and relay output status
V18
Control program
V19
Unit nominal power
V20
Motor temperature rise
V21
Reference frequency
V22
Torque reference
Table 8-1 Monitoring items
Motor Pump Enhanced Protection Application
Possible Cause
Fieldbus board has detected the reset of
error of the Bus system (physical layer)
I/O detected a fault at this input
I/O detected a fault at this input
I/O detected a fault at this input
I/O detected a fault at this input
Unit
Hz
rpm
A
%
%
V
V
°C
DD.dd
HH.hh
MWh
MWh
V
mA
HP
%
Hz
%
Description
Frequency to the motor
Calculated motor speed
Measured motor current
Calculated actual torque/nominal torque of the unit
Calculated actual power/nominal power of the unit
Calculated motor voltage
Measured DC-link voltage
Temperature of the heat sink
1)
Operating days
, not resettable
2)
Operating hours
, can be reset with programmable
button #3
Total MW-hours, not resettable
MW-hours, can be reset with programmable button #4
Voltage of the terminal V
Current of terminals I
+ and I
in
Version number of the control software
Shows the power size of the unit
100%= temperature of motor has risen to nominal
Frequency reference
Torque reference when torque control in use
1)
DD = full days, dd = decimal part of a day
HH = full hours, hh = decimal part of an hour
2)
SV9000
Check
Reset the fault and restart
again. If the fault comes again:
- check the host system
– check the cables
Verify settings in group 11
Verify settings in group 11
Verify settings in group 11
Verify settings in group 11
+ (term. #2)
in
- (term. #4, #5)
in

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents