A. Notes on commissioning and service
A.3
Operation and service
A.3.1 Nominal/actual comparison
Serial numbers have not
been transferred yet.
Serial numbers have been
transferred.
A−18
When switching on, the CMAX compares the setpoint and
actual configuration. How complex this comparison is de
pends on whether the serial numbers of the components
were adopted.
The actual configuration only needs to be compatible with
the setpoint configuration. Deviations lead to error E01.
The actual configuration is compatible if it corresponds with
the hardware configuration within a certain tolerance range.
In this no serial numbers are compared, only the size, supply
pressure and mounting position.
The actual configuration must be compatible with the set
point configuration. The components valve and measuring
system have clearly been assigned to the project. Deviations
lead to fault E01.
The serial numbers of the measuring system/sensor inter
face and valve must correspond with the projected serial
numbers. A deviation leads to warning W08, deviations from
both to fault E01.
The reason for this is the data that depends on the individual
valve and drive which is ascertained during identification and
adaptation.
The serial numbers are transferred when a movement test,
start, or homing is performed for the first time.
The serial numbers and corresponding configuration data are
transferred each time the user performs the identification.
Festo P.BE−CPX−CMA X−CONTROL−EN en 0908NH