FC 300 Design Guide
14-** Special Functions
"
Par.
Parameter description
No.
#
14-0* Inverter Switching
14-00 Switching Pattern
14-01 Switching Frequency
14-03 Overmodulation
14-04 PWM Random
14-1* Mains On/Off
14-12 Function at Mains Imbalance
14-2* Trip Reset
14-20 Reset Mode
14-21 Automatic Restart Time
14-22 Operation Mode
14-25 Trip Delay at Torque Limit
14-28 Production Settings
14-29 Service Code
14-3* Current Limit Ctrl.
14-30 Current Lim Cont, Proportional Gain
14-31 Current Lim Contr, Integration Time
14-4* Energy Optimising
14-40 VT Level
14-41 AEO Minimum Magnetisation
14-42 Minimum AEO Frequency
14-43 Motor Cosphi
14-5* Environment
14-50 RFI Filter
14-52 Fan Control
default setting
( )
*
232
How to Programme
Default value
[1] SFAVM
[0] Manual reset
[0] Normal operation
[0] No action
ExpressionLimit
display text
[ ]
value for use in communication via serial communication port
MG.33.B4.02 - VLT is a registered Danfoss trademark
4-set-up
All set-ups
null
All set-ups
[1] On
All set-ups
[0] Off
All set-ups
[0] Trip
All set-ups
All set-ups
10 s
All set-ups
All set-ups
60 s
All set-ups
All set-ups
0 N/A
All set-ups
100 %
All set-ups
0.020 s
All set-ups
66 %
All set-ups
40 %
All set-ups
10 Hz
All set-ups
All set-ups
[1] On
1 set-up
[0] Auto
All set-ups
FC 302
Change
Conver-
only
during
sion index
operation
TRUE
-
TRUE
-
FALSE
-
TRUE
-
TRUE
-
TRUE
-
TRUE
0
TRUE
-
TRUE
0
TRUE
-
TRUE
0
FALSE
0
FALSE
-3
FALSE
0
TRUE
0
TRUE
0
TRUE
-2
x
FALSE
-
TRUE
-
Type
Uint8
Uint8
Uint8
Uint8
Uint8
Uint8
Uint16
Uint8
Uint8
Uint8
Int32
Uint16
Uint16
Uint8
Uint8
Uint8
Uint16
Uint8
Uint8