FC 300 Design Guide
Control characteristics:
Resolution of output frequency at 0 - 1000 Hz ..................... FC 301: +/- 0.013 Hz / FC 302: +/- 0.003 Hz
Repeat accuracy of Precise start/stop (terminals 18, 19) ............ FC 301: ≤ ± 1ms / FC 302: ≤ ± 0.1 msec
System response time (terminals 18, 19, 27, 29, 32, 33) ...................
Speed control range (open loop) ............................................................... 1:100 of synchronous speed
Speed control range (closed loop) ............................................................ 1:1000 of synchronous speed
Speed accuracy (open loop) ................................................... 30 - 4000 rpm: Maximum error of ±8 rpm
Speed accuracy (closed loop) .............................................. 0 - 6000 rpm: Maximum error of ±0.15 rpm
All control characteristics are based on a 4-pole asynchronous motor
Surroundings:
Enclosure ............................................................................................................................... IP 20
Enclosure kit available ..................................................................................... IP21/TYPE 1/IP 4X top
Vibration test .......................................................................................................................... 1.0 g
Max. relative humidity ................... 5% - 95%(IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 721-3-3), uncoated .................................................................
Aggressive environment (IEC 721-3-3), coated ....................................................................
Ambient temperature ..................................................... Max. 50 °C (24-hour average maximum 45 °C)
Derating for high ambient temperature, see section on special conditions
Minimum ambient temperature during full-scale operation ............................................................
Minimum ambient temperature at reduced performance ...........................................................
Temperature during storage/transport ......................................................................... -25 - +65/70 °C
Maximum altitude above sea level .......................................................................................... 1000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission ................................
EMC standards, Immunity ..................................................................... EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, (EN 50082-1/2)
See section on special conditions
Control card performance:
Scan interval ....................................................................................... FC 301: 10 ms / FC 302: 1 ms
Control card, USB serial communication:
USB standard ............................................................................................................................ 2.0
USB plug .................................................................................................... USB type B "device" plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection earth. Use only isolated laptop
as PC connection to the USB connector on FC 300 drive.
60
How to Select Your VLT
EN 61800-3, EN 61000-6-3/4, EN 55011, (EN 50081-1/2)
MG.33.B4.02 - VLT is a registered Danfoss trademark
FC 301: ≤ 20 ms / FC 302: ≤ 2 ms
class 3C2
class 3C3
0 °C
- 10 °C
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?
Questions and answers