FC 300 Design Guide
Ramp bit 1 [35]
•
Mains failure inverse
•
activate par. 14-10 Mains Failure. Mains failure
inverse is active in the Logic '0' situation.
DigiPot Increase
•
INCREASE signal to the Digital Potientiometer
function described in parameter group 3-9*
DigiPot Decrease
•
DECREASE signal to the Digital Potentiometer
function described in parameter group 3-9*
DigiPot Clear
[57]: Uses the input to
•
CLEAR the Digital Potentiometer reference
described in parameter group 3-9*
Counter A
[60]: (Terminal 29 or 33 only) Input
•
for increment counting in the SLC counter.
Counter A
[61]: (Terminal 29 or 33 only) Input
•
for decrement counting in the SLC counter.
Reset Counter A
•
reset of counter A.
Counter B
[63]: (Terminal 29 or 33 only) Input
•
for increment counting in the SLC counter.
Counter B
[64]: (Terminal 29 or 33 only) Input
•
for decrement counting in the SLC counter.
Reset Counter B
•
reset of counter B.
Speed down
[22]: Same as Speed up [21].
•
Set-up select bit 0 [23]
•
Set-up, bit 0 and bit 1 allows you to choose
between one of the four set-ups. You must
set par. 0-10 to Multi Set-up.
Set-up select bit 1 [24]
•
32): Same as Set-up select bit 0 [23].
•
Catch up
[28]: Select Catch up/Slow
down to increase or reduce the reference
value (set in par. 3-12).
5-10 Terminal 18 Digital Input
*
Start
Function:
5-11 Terminal 19 Digital Input
*
Reversing
5-12 Terminal 27 Digital Input
*
Coast inverse
5-13 Terminal 29 Digital Input
Option:
*
Jog
Counter A (up)
Counter A (down)
Counter B (up)
default setting
( )
*
How to Programme
[36]: Is selected to
[55]: Uses the input as an
[56]: Uses the input as a
[62]: Input for
[65]: Input for
: Selection of
(Default Digital input
[14]
[60]
[61]
[63]
display text
[ ]
value for use in communication via serial communication port
MG.33.B4.02 - VLT is a registered Danfoss trademark
Counter B (down)
Function:
Options [60], [61], [63] and [64] are additional
functions. Counter function is used in Smart
Logic Control functions.
This parameter is only available in FC 302.
5-14 Terminal 32 Digital Input
Option:
*
No operation
Counter A (up)
Counter A (down)
Counter B (up)
Counter B (down)
Function:
Option [60], [61], [63] and [64] are additional
functions. Counter function is used in Smart
Logic Control functions.
5-15 Terminal 33 Digital Input
*
No operation
Counter A (up)
Counter A (down)
Counter B (up)
Counter B (down)
Function:
Options [60], [61], [63] and [64] are additional
functions. Counter function is used in Smart
Logic Control functions.
5-3* Digital Outputs
"
The 2 solid-state digital outputs are common
for terminals 27 and 29. Set the I/O function
for terminal 27 in par. 5-01, and set the I/O
function for terminal 29 in par. 5-02.
These parameters cannot be set while running.
[8]
No operation
Control ready
Drive ready
Drive ready / remote control
[10]
Enable / no warning
VLT running
Running / no warning
Run in range / no warning
[2]
Run on reference / no warning
Alarm
Alarm or warning
At torque limit
Out of current range
Below current, low
Above current, high
Out of range
[64]
[0]
[60]
[61]
[63]
[64]
[0]
[60]
[61]
[63]
[64]
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
167