FC 300 Design Guide
programmed to produce a status signal on the
digital outputs and the relay outputs.
4-58 Missing Motor Phase Function
Option:
Off
*
On
Function:
Selects monitoring of the motor phases. If you
select On, the frequency converter reacts on a
missing motor phase and displays an alarm. If you
select Off, no alarm is returned if a motor phase is
missing. If the motor runs on only two phases, it
can be damaged/overheated. Thus, do not change
the missing motor phase function On. You cannot
set this parameter while the motor is running.
4-6* Speed Bypass
"
Parameters for setting the Speed Bypass
areas for the ramps.
4-60 Bypass Speed From [RPM]
Array [4]
Range:
0 - par. 4-13 RPM
Function:
Some systems call for avoiding certain output
frequencies / speed due to resonance problems
in the system. Enter the frequencies /
speed you want to avoid.
4-62 Bypass Speed To [RPM]
Array [4]
Range:
0 - par. 4-13 RPM
Function:
Some systems call for avoiding certain output
frequencies / speed due to resonance problems
in the system. Enter the frequencies /
speed you want to avoid.
default setting
( )
*
164
How to Programme
[0]
[1]
*
0 RPM
*
display text
[ ]
value for use in communication via serial communication port
MG.33.B4.02 - VLT is a registered Danfoss trademark
0RPM