9.5
Setting Controller Action at Power ON (Restart Mode)
Description
Setting Details
9-6
For details, see Chapter 15, "Power Failure Recovery Processing."
Parameter
Name
symbol
R.MD
Restart Mode
The preset output (PO) is output in MAN or AUTO mode.
Display
Setting range
level
Set how the controller should
recover from a power failure of 5
seconds or more.
STD
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
Menu symbol
SYS
IM 05P01D31-01EN