Setting Retransmission Output Terminal, Type, And Scales - YOKOGAWA UT Advanced UT32A User Manual

Digital indicating controllers
Table of Contents

Advertisement

10.11 Setting Retransmission Output Terminal, Type,
and Scales
Description
Setting Details
10-16
The retransmission output can be used when the control output is not assigned to
the analog output terminal. Confirm the output type selection (OT) before setting the
retransmission output. The range can be changed.
► Control output terminal: 10.1 Setting Control Output Type
► Current output range: 10.14 Changing Current Output Range
Minimum value of
PV input range
0.0°C
PV scale
50.0°C
Retransmission scale
Output range
4 mA
To Recorder
Parameter
Name
symbol
Retransmission
RTS
out type of
RET
Maximum value of
PV input range
200.0°C
150.0°C
20 mA (output signal)
Display
Setting range
level
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to
100 % in Position proportional control)
LPS: 15 V DC loop power supply
EASY
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output
(internal computed value)
PV: PV terminals analog input
Menu symbol
OUT