10.12.3
Setting Output Value When Error Occurs (Input Error Preset Output)
Description
Setting Details
IM 05P01D31-01EN
The 0% control output, 100% control output, or input preset output can be selected and
output as input error preset output in the following conditions.
• The input burnout occurs during operation in AUTO mode and RUN mode.
• The ADC error occurs during operation in AUTO mode and RUN mode.
However, the manual output becomes the output when the input burnout occurs in MAN
mode and RUN mode.
Parameter
Name
symbol
Input error preset
EPO
output
10.12 Setting Preset Output Value
Display
Setting range
level
0: Preset output
STD
1: 0% output
2: 100% output
Menu symbol
SYS
10