10.4 Disabling Output Limiter in MAN mode
Description
Setting Details
IM 05P01D31-01EN
Output limiter can be released when in MAN mode.
However, cannot be released when in Heating/cooling control.
Note that the output bump is caused if the operation mode is changed from MAN to
AUTO while the control output is out of the range between the control output high limit (OH)
and control output low limit (OL).
Control output bumps to OH in MAN mode when it is larger than OH.
Moreover, it bumps to OL when smaller than OL.
Parameter
Name
symbol
OLMT
Output limiter switch
Display
Setting range
level
OFF: Disable output limiter in
MAN mode
PRO
ON: Enable output limiter in
MAN mode
Menu symbol
TUNE
10