Description:
This parameter adjusts the current level (DC braking torque) applied to the motor during the braking.
The programmed current level is a percentage of the inverter rated current.
This parameter works only in the Sensorless Vector control mode.

12.9 SKiP SPeeD [48]

The parameters of this group prevent the motor from operating permanently at speed values where, for instance,
the mechanic system enters in resonance (causing exaggerated vibration or noise).
P0303 – Skip Speed 1
Adjustable
0 to 18000 rpm
Range:
P0304 – Skip Speed 2
Adjustable
0 to 18000 rpm
Range:
P0305 – Skip Speed 3
Adjustable
0 to 18000 rpm
Range:
P0306 – Skip Band
Adjustable
0 to 750 rpm
Range:
Proprieties:
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
This actuation of these parameters occurs as presented in the figure 12.12 next.
The passage through the avoided speed range (2 x P0306) takes place by means of the acceleration/deceleration
ramps.
The function does not operate properly if two bands of "Skip Speed" overlap.
48 Skip Speed
Functions Common to All the Control Modes
Factory
600 rpm
Setting:
Factory
900 rpm
Setting:
Factory
1200 rpm
Setting:
Factory
0 rpm
Setting:
12-21
12