Faults and Alarms
Description:
This parameter must be kept always in 1 (On). Only in special maintenance cases the value 0 (Off) can be used.
P0357 – Line Phase Loss time
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
It configures the time for the line phase loss indication (F006).
If P0357=0, the function remains disabled.
P0359 – Motor current Stabilization
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
The parameter P0359 allows enabling the motor current stabilizing function.
This function eliminates oscillations in the motor current caused by operation at low speeds with little load.
P0800 - Phase U Book 1 temperature
P0801 - Phase V Book 1 temperature
P0802 - Phase W Book 1 temperature
P0803 - Phase U Book 2 temperature
P0804 - Phase V Book 2 temperature
P0805 - Phase W Book 2 temperature
P0806 - Phase U Book 3 temperature
15
P0807 - Phase V Book 3 temperature
P0808 - Phase W Book 3 temperature
15-14
0 to 60 s
01 PARAMETER GROUPS
45 Protections
0 = Off
1 = On
V/f and VVW
01 PARAMETER GROUPS
45 Protections
Factory
3 s
Setting:
Factory
0
Setting: