Vector Control
11
11-34
Seq.
Action/Result
At this point, the keypad
(HMI) presents the option to
run the "Self-Tuning".
Whenever possible the Self-
Tuning must be carried out.
- Thus, press "Select" to
20
access P0408 and then
to select the
desired option. Refer to the
section 11.8.5 for more
details.
- Next press "Save".
- After doing that the Self-
Tuning routine is initiated
and "SelfTun" is indicated
on the top left corner of the
keypad (HMI).
21
- If the chosen option had
been the option 1, 2 or
3 in P0408, the keypad
(HMI) will present "P0409:
Estimating Rs".
The keypad (HMI) will also
indicate the estimation of
the parameters P0411,
P0410 and P0412 (if the
option 1, 2 or 3 had been
chosen in P0408).
- When P0408 = 1 or
3 the keypad (HMI) will
not indicate the P0410
estimation.
22
- When P0408 = 3 or 4 the
keypad (HMI) will indicate
the P0413 estimation.
- Wait until the end of the
Self-Tuning routine.
Once the Self-Tuning
routine has finished, the
inverter returns to the
23
monitoring mode.
Figure 11.6 - Vector mode Oriented Start-up (cont.)
Display Indication
Config
0rpm
LOC
Motor Ventilation
P0406: Self-Vent.
Run Self-Tuning
P0408: No
13:48
Select
SelfTun
0rpm
LOC
P0409
Estimating Rs
[001] No Rotation
13:48
SelfTun
0rpm
LOC
P0411
Estimating σls
13:48
SelfTun
0rpm
LOC
P0410
Estimating Im
13:48
SelfTun
LOC
0rpm
P0412
Estimating Tr
13:48
SelfTun
0rpm
LOC
P0413
Estimating Tm
13:48
Ready
LOC
0rpm
0
rpm
4.0
A
0.0
Hz
13:48
Menu