WEG CFW-11 Programming Manual page 238

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Trace Function [52]
The memory area used by the Trace Function is shared with the memory for the SoftPLC applicative. When there is a
SoftPLC applicative in the inverter, the amount of memory actually available for the Trace Function may be smaller
than the value adjusted in P0559. The indication of the memory amount actually available is done by the read only
parameter P0560. For more details refer to the parameter P0560 description.
As the factory setting, P0559=0 %. In this case, there is no memory available for the Trace Function, because the
available 15 KB are reserved for the SoftPLC applicative.
P0560 – trace available Memory
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
It shows the amount of memory available for storing Trace Function points. The range from 0 to 100 % indicates that
from 0 to 15 KB are available for the Trace Function.
Sharing of memory with the SoftPLC:
The memory for the Trace Function is shared with the memory for the SoftPLC applicative.
- If P1000=0 (there is no SoftPLC applicative), it is possible to use all the memory area for the Trace Function. In
this case, P0559=P0560.
- If P1000>0 (there is SoftPLC applicative in the inverter), P0560 will show the smallest value between P0559 and
0the actual available memory (that will be 100 % minus the memory used by the SoftPLC applicative).
In order to be able to use the Trace Function, the user must adjust P0559 to a value different from 0 %, and verify if
the value indicated in P0560 is enough. If P0559 > P0560 and the user wishes to use more memory for the Trace
Function, then the SoftPLC applicative must be erased by means of the parameter P1001.
P0561 – cH1: trace channel 1
P0562 – cH2: trace channel 2
P0563 – cH3: trace channel 3
P0564 – cH4: trace channel 4
Adjustable
Range:
19
19-4
0 to 100 %
RO
01 PARAMETER GROUPS
52 Trace Function
0 = Not selected
1 = Speed Reference
2 = Motor Speed
3 = Motor Current
4 = DC Link Voltage
5 = Motor Frequency
6 = Motor Voltage
7 = Motor Torque
8 = Process Variable
9 = PID Setpoint
10 = AI1
11 = AI2
12 = AI3
13 = AI4
Factory
Setting:
Factory
P0561=1
Setting:
P0562=2
P0563=3
P0564=0