Faults and Alarms
P0352 – fan control
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
The CFW-11 is equipped with two fans: an internal fan and a heatsink fan, and the activation of both will be
controlled via software by means of the inverter programming.
The options available for the setting of this parameter are the following:
15
15-12
0 = Heatsink fan and internal fan are OFF
1 = Heatsink fan and internal fan are ON
2 = Heatsink fan and internal fan are controlled via software
3 = Heatsink fan is controlled via software and internal fan is OFF
4 = Heatsink fan is controlled via software and internal fan is ON
5 = Heatsink fan is ON and internal fan is OFF
6 = Heatsink fan is ON and internal fan is controlled via software
7 = Heatsink fan is OFF and internal fan is ON
8 = Heatsink fan is OFF and internal fan is controlled via software
CFG
01 PARAMETER GROUPS
45 Protections
Table 15.5 - Options of the parameter P0352
P0352
0 = HS-OFF, Int-OFF
1 = HS-ON, Int-ON
2 = HS-CT, Int-CT
3 = HS-CT, Int-OFF
4 = HS-CT, Int-ON
5 = HS-ON, Int-OFF
6 = HS-ON, Int-CT
7 = HS-OFF, Int-ON
8 = HS-OFF, Int-CT
Action
Heatsink fan is always OFF.
Internal fan is always OFF.
Heatsink fan is always ON.
Internal fan is always ON.
Heatsink fan is controlled via software.
Internal fan is controlled via software.
Heatsink fan is controlled via software.
Internal fan is always OFF.
Heatsink fan is controlled via software.
Internal fan is always ON.
Heatsink fan is always ON.
Internal fan is always OFF.
Heatsink fan is always ON.
Internal fan is controlled via software.
Heatsink fan is always OFF.
Internal fan is always ON.
Heatsink fan is always OFF.
Internal fan is controlled via software.
Factory
2
Setting: