Functions Common to All the Control Modes
t0 – Line loss;
t1 – Line loss detection;
t2 – Undervoltage actuation (F021 without Ride-Through);
t3 – Line return;
t4 – Line return detection;
t5 – Undervoltage actuation (F021 with Ride-Through).
If the line voltage produces an U
may occur, the values of P0321, P0322 and P0323 must be readjusted.
Note!
When one of the functions, Ride-Through or Flying Start, is activated, the parameter P0357 (Line
Phase Loss Time) is ignored, regardless of the adjusted time.
Note!
Cautions with the application:
It is mandatory the use of a line reactor to limit the inrush current when the line returns;
Use oversized Ultra-Rapid fuses or normal fuses for the same reason.
Note!
The Ride-Through function activation occurs when the power supply voltage is lower than the value
(P0321/1.35).
U
=VAC x 1.35
d
P0321 – Dc Link Power Loss
Adjustable
Range:
P0322 – Dc Link Ride-through
Adjustable
Range:
12
12-16
voltage between the values adjusted in P0322 and P0323, the fault F0150
d
178 to 282 V
308 to 616 V
308 to 616 V
308 to 616 V
308 to 616 V
425 to 737 V
425 to 737 V
486 to 885 V
486 to 885 V
178 to 282 V
308 to 616 V
308 to 616 V
308 to 616 V
308 to 616 V
425 to 737 V
425 to 737 V
486 to 885 V
486 to 885 V
Factory
P0296=0: 252 V
Setting:
P0296=1: 436 V
P0296=2: 459 V
P0296=3: 505 V
P0296=4: 551 V
P0296=5: 602 V
P0296=6: 660 V
P0296=7: 689 V
P0296=8: 792 V
Factory
P0296=0: 245 V
Setting:
P0296=1: 423 V
P0296=2: 446 V
P0296=3: 490 V
P0296=4: 535 V
P0296=5: 585 V
P0296=6: 640 V
P0296=7: 668 V
P0296=8: 768 V