WEG CFW-11 Programming Manual page 122

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Vector Control
P0181 – Magnetization Mode
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
In the sensorless vector control mode, the magnetizing current is permanently active. In order to disable it when
the motor is stopped, a digital input programmed for General Enabling can be used. There is also the possibility
of programming P0217 in 1 (active). Refer to the section 12.6. Besides this, a delay for disabling the magnetizing
current can be set by programming P0219 bigger than zero.
P0188 – Proportional Gain of the Maximum output Voltage Regulator
P0189 – integral Gain of the Maximum output Voltage Regulator
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
These parameters adjust the maximum output voltage regulator gains. In general the factory setting is adequate for
the majority of the applications.
P0190 – Maximum output Voltage
Adjustable
Range:
Proprieties:
11
Access groups
via HMI:
11-20
0 = General Enable
1 = Run/Stop
CFG and Encoder
01 PARAMETER GROUPS
29 Vector Control
92 Flux Regulator
Table 11.4 - Magnetization Mode
P0181
0 = General Enable
Applies magnetizing current after General Enabling = ON
1 = Run/Stop
Applies magnetizing current after Run/Stop = Run
0.000 to 7.999
Vector
01 PARAMETER GROUPS
29 Vector Control
92 Flux Regulator
0 to 690 V
Vector
01 PARAMETER GROUPS
29 Vector Control
92 Flux Regulator
Factory
Setting:
Action
Factory
Setting:
Factory
0.95 x P0296.
Setting:
Automatic setting
during the Oriented
Start-up Routine:
0.95 x P0400.
0
P0188=0.200
P0189=0.001