Inverter Programming; Symbols For The Proprieties Description; P0105 - 1St/2Nd Ramp Selection; P0220 - Local/Remote Selection Source - WEG CFW-11 Communications Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

3 Inverter Programming

Next, only the CFW-11 frequency inverter parameters related to the CANopen communication will be presented.

3.1 Symbols for the Proprieties Description

RO
Read-only parameter.
CFG
Parameter that can be changed only with a stopped motor.
Parameter visible on the HMI if the inverter has the network interface installed – RS232, RS485,
Net
CAN, Anybus-CC, Profibus – or if the USB interface is connected.
Serial
Parameter visible on the HMI if the inverter has the RS232 or RS485 interface installed.
CAN
Parameter visible on the HMI if the inverter has the CAN interface installed.
P0105 – 1st/2nd Ramp Selection
P0220 – Local/Remote Selection Source
P0221 – Speed Reference Selection – Local Situation
P0222 – Speed Reference Selection – Remote Situation
P0223 – Selection of the Rotation Direction - Local Situation
P0224 – Start/Stop Selection – Local Situation
P0225 – Jog Selection - Local Situation
P0226 – Selection of the Rotation Direction - Remote Situation
P0227 – Start/Stop Selection – Remote Situation
P0228 – Jog Selection - Remote Situation
These parameters are used in the configuration of the source of commands for the local and remote mode of the
inverter CFW-11. So that the inverter is controlled through the CANopen interface, one of the available
'CANopen/DNet' in the parameters options must be selected.
The detailed description of these parameters are found in the Programming the CFW-11 Manual.
P0313 – Communication Error Action
Range:
0 = Off
1 = Ramp stop
2 = General disable
3 = Change to LOCAL
4 = Change to LOCAL keeping the commands and the reference
5 = Fault trip
Proprieties:
CFG, Net
Access groups via HMI:
01 PARAMETER
GROUPS.
∟ 49 Communication
∟ 111
Status/Commands.
Description:
It allows the selection of the action to be executed by the inverter when a communication error is detected.
.
Default:
0

Advertisement

Table of Contents
loading

Table of Contents