WEG CFW-11 Programming Manual page 187

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Description:
It specifies the value in rpm where the Actual Speed will be considered null for the actuation of the Zero Speed Disable
function.
This parameter is also used for the functions: Digital and relay outputs, and by the PID regulator.
P0292 – N = N* Band
Adjustable
0 to 18000 rpm
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
It is used in the N = N* function of the digital and relay outputs.
P0293 – tx torque
Adjustable
0 to 200 %
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
It is used in the Torque > Tx and Torque < Tx functions of the digital and relay outputs.
In those functions the motor torque indicated in P0009 is compared with the value adjusted in P0293.
The setting of this parameter is expressed as a percentage of the motor rated current (P0401=100 %).
P0294 – Hx time
Adjustable
0 to 6553 h
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
It is used in the Enabled Hours > Hx function of the digital and relay outputs.
41 Digital Outputs
41 Digital Outputs
41 Digital Outputs
Digital and Analog Inputs and Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
18 rpm
(15 rpm)
100 %
4320 h
13