P0809 - Phase U Book 4 temperature
P0810 - Phase V Book 4 temperature
P0811 - Phase W Book 4 temperature
P0812 - Phase U Book 5 temperature
P0813 - Phase V Book 5 temperature
P0814 - Phase W Book 5 temperature
Adjustable
-20.0 °C to 150.0 °C
Range:
Proprieties:
RO
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
These read only parameters indicate, in Celsius degrees (°C), the internal temperature of the IGBTs of each phase of
each book. The indication resolution is 0.1 °C. Refer to the CFW-11M User Manual to obtain more information.
P0832 - Digital input DiM1 function
P0833 - Digital input DiM2 function
Adjustable
0 = Not Used
Range:
1 = External Fault
2 = Refrigeration Fault
3 = Braking Resistor Overtemperature
4 = Rectifier Overtemperature
5 = Rectifier High Temperature
Proprieties:
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
These parameters allow configuring the digital inputs DIM1 and DIM2 with the type of fault (0 to 4) or alarm (5) that
must be recognized by the control, signalized on the keypad (HMI), and for the options 0 to 4, cause the disabling
of the inverter.
45 Protections
45 Protections
Factory
Setting:
or
09 READ ONLY PARAMETERS
Factory
Setting:
or
01 PARAMETER GROUPS
40 Digital Inputs
Faults and Alarms
0