Table 13.6 - Configuration of the analog outputs AO1 and AO2 signals
Table 13.7 - Configuration of the analog outputs AO3 and AO4 signals
P0259, P0262
For AO1 and AO2, when current signals are used, the switch corresponding to the desired output must be set in the
"ON" position.
For AO3 and AO4, when current signals are used, the outputs AO3 (I) and AO4 (I) must be used. For voltage signals
use the outputs AO3 (V) and AO4 (V). The switch corresponding to the desired output must be set in "ON" only in
order to use range from -10 V to +10 V .

13.1.3 Digital inputs [40]

The CFW-11 has 6 digital inputs in the standard version, and 2 more can be added with the IOA-01 and
IOB-01 accessories. The parameters that configure those inputs are presented next.
P0012 – Di8 to Di1 Status
Adjustable
Bit 0 = DI1
Range:
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
Proprieties:
RO
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
By means of this parameter it is possible to visualize the status of the 6 control board digital inputs (DI1 to DI6) and
of the 2 accessory digital inputs (DI7 and DI8) as well.
Table 13.5 - DIP switches related to the analog outputs
Parameter
Output
P0253
AO1
P0256
AO2
P0259
AO3
P0262
AO4
P0253, P0256
Output Signal
0
(0 to 10) V / (0 to 20) mA
1
(4 to 20) mA
2
(10 to 0) V / (20 to 0) mA
3
(20 to 4) mA
Output Signal
0
0 to 20 mA
1
4 to 20 mA
2
20 to 0 mA
3
20 to 4 mA
4
0 to 10 V
5
10 to 0 V
6
-10 to +10 V
40 Digital Inputs
Digital and Analog Inputs and Outputs
Switch
Location
S1.1
Control Board
S1.2
S2.1
IOA
S2.2
Switch Position
Off / On
On
Off / On
On
Switch Position
or
01 PARAMETER GROUPS
40 Digital Inputs
Off
Off
Off
Off
Off
Off
On
Factory
Setting:
13
13-11