b) Prepare the inverter and apply power: according to the section 5.1 of the CFW-11 User Manual.
c) Adjust the password P0000=5: according to the section 5.3 of this manual.
d) Adjust the inverter to operate with the application line and motor: by means of the "Oriented Start-up"
Menu access P0317 and change its content to 1, which makes the inverter initiate the "Oriented Start-up"
routine.
The "Oriented Start-up" routine presents on the keypad (HMI) the main parameters in a logical sequence. The
setting of these parameters prepares the inverter for operation with the application line and motor. Verify the
step by step sequence in the figure 10.2.
The setting of the parameters presented in this operation mode results in the automatic modification of the
content of other inverter parameters and/or internal variables, as indicated in the figure 10.2. In this way one
gets a stable operation of the control circuit with adequate values to obtain the best motor performance.
During the "Oriented Start-up" routine the "Config" (Configuration) status will be indicated on the top left part
of the keypad (HMI).
Parameters related to the motor:
- Program the contents of parameters from P0398 to P0407 directly with the motor nameplate data. Refer
to the section 11.7 (Motor Data).
- Options for the setting of parameter P0409:
I – Automatic by the inverter, performing the self-tuning routine selected in P0408.
II – From the motor test data sheet, supplied by the manufacturer. Refer to the section 11.7.1 in this
manual.
III – Manually, copying the parameters content of another CFW-11 that runs an identical motor.
e) Setting of specific parameters and functions for the application: program the digital and analog
inputs and outputs, HMI keys, etc., according to the application needs.
For applications:
- That are simple, which can use the factory settings programming for the digital and analog inputs and
outputs, use the Menu "Basic Application". Refer to the section 5.2.3 of the CFW-11 User Manual.
- That require only the digital and analog inputs and outputs with programming different from the factory
settings, use the Menu "I/O Configuration".
-That need functions as Flying Start, Ride-Through, DC Braking, Dynamic Braking, etc., access and modify
those function parameters by means of the Menu "Parameter Groups".
VVW Control
10
10-5