Functions Common to All the Control Modes
Line Returns
P0332
Disabled
a) with the line returning before the time adjusted in P0332
The actuation of the Ride-Through function can be visualized at the outputs DO1/RL1, DO2/RL2, DO3/RL3,
DO4 and/or DO5 (P0275 to P0279), provided that they have been programmed in "24=Ride-Through".
P0331 – Voltage Ramp
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
This parameter sets the necessary time for the output voltage to reach the rated voltage value.
It is used by the Flying Start function as well as by the Ride-Through function (both in V/f mode), together with the
parameter P0332.
P0332 – Dead time
Adjustable
Range:
Proprieties:
12
Access groups
via HMI:
12-14
DC Link Voltage
F021 Level
Enabled
Output Pulses
P0331
Output Voltage
0 V
Output Speed
(P0002)
0 rpm
Figure 12.6 - Ride-Through actuation in V/f mode
0.2 to 60.0 s
V/f and VVW
01 PARAMETER GROUPS
44 FlyStart/RideThru
0.1 to 10.0 s
V/f and VVW
01 PARAMETER GROUPS
44 FlyStart/RideThru
Line Returns
Enabled
P0332
P0331
Disabled
b) with the line returning after the time adjusted in P0332, but
before 2 s (for P0332 ≤ 1 s), or before 2 x P0332
(for P0332 > 1 s)
DC Link Voltage
F021 Level
Output Pulses
Time adjusted in P0332
Output Voltage
0 V
Output Speed (P0002)
0 rpm
Factory
2.0 s
Setting:
Factory
1.0 s
Setting: