Functions Common to All the Control Modes
Description:
The Multispeed brings as advantages the stability of the predefined fixed references, and the immunity against
electric noises (isolated digital inputs DIx).
In order to activate the Multispeed function one must configure the parameter P0221=8 and/or P0222=8
(Reference Selection).
In order to use only 2 or 4 speeds, any combination of the DI4, DI5 and DI6 inputs can be used. Verify the Speed
Reference parameters according to the used DI's.
The input(s) programmed for other function(s) must be considered as 0 V, as presented in the table 12.4.
DI6
0 V
0 V
0 V
0 V
24 V
24 V
24 V
24 V
12
12-8
Table 12.3 - Multispeed function selection via digital inputs
Enabled DIx
DI4
DI5
DI6
Table 12.4 - Multispeed reference
8 speeds
DI5
0 V
0 V
24 V
24 V
0 V
0 V
24 V
24 V
Output speed
P0129
P0128
P0127
P0126
P0125
P0124
DI6
DI5
DI4
Figure 12.4 - Multispeed
Programming
P0266=13
P0267=13
P0268=13
4 speeds
2 speeds
DI4
0 V
24 V
0 V
24 V
0 V
24 V
0 V
24 V
P0130
P0131
Accelerating ramp
Time
24 V
0 V (open)
24 V
0 V (open)
24 V
0 V (open)
Speed Reference
P0124
P0125
P0126
P0127
P0128
P0129
P0130
P0131