Quick Parameter Reference, Faults and Alarms
0
Parameter
Function
P0270
DI8 Function
P0275
DO1 Function (RL1)
0-12
Adjustable Range
Factory Setting
0 = Not Used
0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Fast Stop
4 = FWD Run
5 = REV Run
6 = 3-Wire Start
7 = 3-Wire Stop
8 = FWD/REV
9 = LOC/REM
10 = JOG
11 = Increase EP
12 = Decrease EP
13 = Not Used
14 = Ramp 2
15 = Speed/Torque
16 = JOG+
17 = JOG-
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 = Not Used
22 = Manual/Auto
23 = Not Used
24 = Disab.FlyStart
25 = DC Link Regul.
26 = Parametriz.Off
27 = Load User 1/2
28 = Load User 3
29 = DO2 Timer
30 = DO3 Timer
31 = Trace Function
0 = Not Used
13 = No Fault
1 = N* > Nx
2 = N > Nx
3 = N < Ny
4 = N = N*
5 = Zero Speed
6 = Is > Ix
7 = Is < Ix
8 = Torque > Tx
9 = Torque < Tx
10 = Remote
11 = Run
12 = Ready
13 = No Fault
14 = No F070
15 = No F071
16 = No F006/21/22
17 = No F051/54/57
18 = No F072
19 = 4-20mA OK
20 = P0695 Value
21 = Forward
22 = Proc. V. > PVx
23 = Proc. V. < PVy
24 = Ride-Through
25 = Pre-Charge OK
26 = Fault
27 = Time Enab > Hx
28 = SoftPLC
29 = Not Used
30 = N>Nx/Nt>Nx
31 = F > Fx (1)
32 = F > Fx (2)
33 = STO
34 = No F160
35 = No Alarm
36 = No Fault and No
Alarm
37 = PLC11
User
Proprieties
Groups
Setting
CFG
20, 31, 32,
33, 34, 37,
40, 44, 45,
46
CFG
41
Pag.
13-12
13-19