Fault/Alarm
F153:
Internal air overtemperature fault.
Internal Air
Overtemperature
F156:
Undertemperature fault (below -30 °C (-22 °F)) in
Undertemperature
the IGBT or rectifier measured by the temperature
sensors.
F161:
Refer to the PLC11-01 Module Programming Manual
Timeout PLC11CFW-11
A162:
Incompatible PLC
Firmware
A163
It indicates that the AI1 current (4 20mA or 20-4mA)
Break Detect AI1
reference is out of the 4 to 20mA range.
A164
It indicates that the AI2 current (4 20mA or 20-4mA)
Break Detect AI2
reference is out of the 4 to 20mA range.
A165
It indicates that the AI3 current (4 20mA or 20-4mA)
Break Detect AI3
reference is out of the 4 to 20mA range.
A166
It indicates that the AI4 current (4 20mA or 20-4mA)
Break Detect AI4
reference is out of the 4 to 20mA range.
A177:
Fan replacement alarm (P0045 > 50000 hours).
Fan Replacement
Note:
This function may be disabled by setting P0354=0.
F179:
This fault indicates a problem with the heatsink fan.
Heatsink Fan Speed Fault
Note:
This function may be disabled by setting P0354=0.
A181:
Invalid clock value alarm.
Invalid Clock Value
F182:
Indicates a fault on the output pulses feedback.
Pulse Feedback Fault
F183:
Overtemperature related to the IGBTs overload
IGBT Overload +
protection.
Temperature
F185
It indicates fault at the Pre charge Contactor
Precharge Contac Fault
F228
Refer to the RS-232 / RS-485 Serial Communication Manual
Serial Communication
Timeout
F229
Refer to the Anybus-CC Communication Manual
Anybus Offline
F230
Anybus Access Error
F233
Refer to the CANopen Communication Manual and/or the DeviceNet Communication Manual
CAN Bus Power Failure
F234
Bus Off
F235
Refer to the CANopen Communication Manual
CANopen Communication
Error
F236
Refer to the DeviceNet Communication Manual
Master Idle
F237
DeviceNet Connect
Timeout
A300:
High temperature alarm measured with the
High temperature at IGBT
temperature sensor (NTC) of the book 1 U phase
U B1
IGBT
F301:
Overtemperature fault measured with the temperature
Overtemperature at IGBT
sensor (NTC) of the book 1 U phase IGBT
U B1
Quick Parameter Reference, Faults and Alarms
Description
Possible Causes
Surrounding air temperature too high (>50 °C (122 °F))
and excessive output current.
Defective internal fan (if installed).
Surrounding air temperature ≤ -30 °C (-22 °F).
Broken AI1 cable;
Bad contact at the signal connection to the terminal strip
Broken AI2 cable;
Bad contact at the signal connection to the terminal strip
Broken AI3 cable;
Bad contact at the signal connection to the terminal strip
Broken AI4 cable;
Bad contact at the signal connection to the terminal strip
Maximum number of operating hours for the heatsink fan
has been reached.
Dust on fan blades and bearings.
Defective fan.
It is necessary to set date and time at parameters P0194
to P0199.
Keypad battery is discharged, defective, or not installed.
Defect in the inverter internal circuitry.
Surrounding air temperature too high.
Operation with frequencies < 10 Hz under overload.
Pre-charge contactor defect
High ambient temperature (>45°C) and high output
current.
Blocked or defective fan.
Fins of the book heatsink too dirty, impairing the air flow.