Functions Common to All the Control Modes
P0121 – Keypad Reference
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
When the
speed reference.
The value of P0121 will be kept with the last adjusted value when the inverter is disabled or powered off, provided
that the parameter P0120 is configured as Active (1).
P0122 – joG Speed Reference
Adjustable
Range:
Proprieties:
Access groups
via HMI:
Description:
During the JOG command the motor accelerates up to the value defined in P0122 following the adjusted acceleration
ramp.
The source of the JOG command is defined in the parameters P0225 (Local Situation) or P0228 (Remote
Situation).
If the JOG command source has been defined for the digital inputs (DI1 to DI8), one of these inputs must be
programmed as presented in the table 12.1.
For more details refer to the figure 13.6 (h).
The speed direction is defined by the parameters P0223 or P0226.
12
The JOG command is effective only with the motor stopped.
For the JOG+ refer to the description below.
12-4
0 to 18000 rpm
01 PARAMETER GROUPS
21 Speed References
and
HMI keys are active (P0221 or P0222=0), this parameter sets the value of the motor
0 to 18000 rpm
01 PARAMETER GROUPS
21 Speed References
Table 12.1 - JOG command via digital input selection
Digital Input
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Factory
Setting:
Parameters
P0263=10 (JOG)
P0264=10 (JOG)
P0265=10 (JOG)
P0266=10 (JOG)
P0267=10 (JOG)
P0268=10 (JOG)
P0269=10 (JOG)
P0270=10 (JOG)
90 rpm
Factory
150 rpm
Setting:
(125 rpm)