Seq.
Action/Result
- If necessary, change the
content of P0296 according
to the used line voltage.
Therefore press "Select".
10
This change will affect
P0151, P0153, P0185,
P0321, P0322, P0323 and
P0400.
- If necessary, change the
content of P0298 according
to the inverter application.
Therefore press "Select".
This change will affect
P0156, P0157, P0158,
11
P0169, P0170, P0401
and P0404. The actuation
time and level of the IGBTs
overload protection will also
be affected.
- If necessary adjust the
content of P0398 according
to the motor service factor.
Therefore press "Select".
This change will affect the
12
current value and the time
for the actuation of the
motor overload function.
If necessary, change the
content of P0400 according
to the rated motor voltage.
Therefore press "Select".
13
This change will affect
P0190.
- If necessary, change the
content of P0401 according
to the rated motor current.
Therefore press "Select".
14
This change will affect
P0156, P0157 and P0158.
Display Indication
Config
0rpm
LOC
Type of Control
P0202: Sensorless
Line Rated Voltage
P0296: 440 - 460 V
13:48
Select
Config
0rpm
LOC
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Normal Duty
13:48
Select
Config
0rpm
LOC
Application
P0298: Normal Duty
Motor Service Factor
P0398:
1.15
13:48
Select
Config
0rpm
LOC
Motor Service Factor
P0398:
1.15
Motor Rated Voltage
P0400:
440V
13:48
Select
Config
0rpm
LOC
Motor Rated Voltage
P0400:
440V
Motor Rated Current
P0401:
13.5 A
13:48
Select
Figure 11.6 - Vector mode Oriented Start-up (cont.)
Seq.
Action/Result
- If necessary, change the
content of P0402 according
to the rated motor speed.
Therefore press "Select".
This change will affect
15
P0122 to P0131, P0133,
P0134, P0182, P0208,
P0288 and P0289.
- If necessary, change the
content of P0403 according
to the rated motor
16
frequency. Therefore press
"Select". This change will
affect P0402.
- If necessary, change the
content of P0404 according
to the rated motor power.
17
Therefore press "Select".
- This parameter will only be
visible if the encoder board
ENC1 is connected to the
inverter.
- If there is an encoder
connected to the motor,
18
change P0405 according
to its number of pulses per
revolution. Therefore press
"Select".
- If necessary, change
the content of P0406
according to the type of
motor ventilation. Therefore
19
press "Select". This change
will affect P0156, P0157,
P0158, P0399 and P0407.
Vector Control
Display Indication
Config
LOC
0rpm
Motor Rated Current
P0401:
13.5A
Motor Rated Speed
P0402= 1750rpm
13:48
Select
Config
0rpm
LOC
Motor Rated Speed
P0402:
1750 rpm
Motor Rated Frequency
P0403: 60Hz
13:48
Select
Config
LOC
0rpm
Motor Rated Frequency
P0403:
60Hz
Motor Rated Power
P0404:
7.5hp
13:48
Select
Config
0rpm
LOC
Motor Rated Power
P0404: 7.5hp
Encoder Pulses Number
P0405: 1024 ppr
13:48
Select
Config
LOC
0rpm
Encoder Pulses Number
P0405: 1024 ppr
Motor Ventilation
P0406: Self-Vent.
13:48
Select
11-33
11