WEG CFW-11 Programming Manual page 227

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Description:
It indicates the state of the digital inputs at the moment of the last fault occurrence.
The indication is done by means of an hexadecimal code, which when converted to binary will indicate the states
"active" and "inactive" of the inputs through numbers 1 and 0.
Example: If the code presented for the parameter P0096 on the keypad (HMI) is 00A5, it will correspond to the
sequence 10100101, indicating that the inputs 8, 6, 3 and 1 were active at the moment of the last fault
occurrence.
Table 16.2 - Example of correspondence between the P0096 hexadecimal code and the DIx states
0
0
0
0
0
0
0
0
0
No relation with the DIx
(always zero)
P0097 – Dox Status at the Moment of the Last fault
Adjustable
Bit 0 = DO1
Range:
Bit 1 = DO2
Bit 2 = DO3
Bit 3 = DO4
Bit 4 = DO5
Proprieties:
RO
Access groups
08 FAULT HISTORY
via HMI:
Description:
It indicates the state of the digital outputs at the moment of the last fault occurrence.
The indication is done by means of an hexadecimal code, which when converted to binary will indicate the states
"active" and "inactive" of the outputs through numbers 1 and 0.
Example: If the code presented for the parameter P0097 on the keypad (HMI) is 001C, it will correspond to the
sequence 00011100, indicating that the outputs 5, 4, and 3 were active at the moment of the last fault
occurrence.
Table 16.3 - Example of correspondence between the P0097 hexadecimal code and the DOx states
0
0
0
0
0
0
0
0
0
No relation with the DOx
(always zero)
P0800 - Phase U Book 1 temperature
P0801 - Phase V Book 1 temperature
P0802 - Phase W Book 1 temperature
P0803 - Phase U Book 2 temperature
A
0
1
0
DI8
DI7
DI6
Active
Inactive
Active
(+24 V)
(0 V)
(+24 V)
1
0
0
0
0
No relation with the DOx
(always zero)
Read Only Parameters [09]
1
0
0
DI5
DI4
Inactive
Inactive
(0 V)
(0 V)
1
1
DO5
DO4
Active
Active
(+24 V)
(+24 V)
5
1
0
1
DI3
DI2
DI1
Active
Inactive
Active
(+24 V)
(0 V)
(+24 V)
Factory
Setting:
C
1
0
0
DO3
DO2
DO1
Active
Inactive
Inactive
(+24 V)
(0 V)
(0 V)
16-13