P0281 – fx frequency
Adjustable
0.0 to 300.0 Hz
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
It is used in the digital output and relay functions:
F>Fx
and F>Fx
(1)
(2)
P0282 – fx Hysteresis
Adjustable
0.0 to 15.0 Hz
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
It is used in the digital output and relay functions:
F > Fx
and F>Fx
(1)
(2)
P0283 – Do2 on time
P0284 – Do2 off time
P0285 – Do3 on time
P0286 – Do3 off time
Adjustable
0.0 to 300.0 s
Range:
Proprieties:
Access groups
07 I/O CONFIGURATION
via HMI:
Description:
Those parameters are used in relay outputs 2 and 3 Timer functions, they adjust the time for the activation or
deactivation of the relay after a transition of the digital input programmed for this function, as detailed in the
parameters of the previous section.
Thus, after a DIx transition for activating or deactivating the programmed relay, it is necessary that this DIx remains
in On/Off for at least the time adjusted in the parameters P0283/P0285 and P0284/P0286. Otherwise the timer
will be reset. Refer to the figure 13.5.
41 Digital Outputs
41 Digital Outputs
41 Digital Outputs
Digital and Analog Inputs and Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
Factory
Setting:
or
01 PARAMETER GROUPS
41 Digital Outputs
4.0 Hz
2.0 Hz
0.0 s
13
13-25