WEG CFW-11 Programming Manual page 100

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

VVW Control
Seq.
Action/Result
- Monitoring Mode.
1
- Press " Menu "
(right "soft key").
- The group "00 ALL
PARAMETERS" is already
2
selected.
- The group "01
PARAMETER GROUPS" is
3
selected.
- The group "02
ORIENTED START-UP" is
4
then selected.
- Press "Select".
- The parameter
"Oriented Start-up
5
P0317:No" is already
selected.
- Press "Select".
- The content of
"P0317 = [000] No" is
6
showed.
- The content of the
parameter is changed to
7
"P0317 = [001] Yes"
- Press "Save".
- In this moment the
Oriented Start-up routine is
initiated and the "Config"
status is indicated at the
top left part of the keypad
(HMI).
- The parameter
"Language P0201:
English" is already
8
selected.
- If necessary, change
the language by pressing
"Select", next
to select the language and
10
then press "Save".
10-6
Display Indication
Ready
0rpm
LOC
0
rpm
0.0
A
0.0
Hz
13:48
Menu
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
13:48
Select
Ready
0rpm
LOC
Oriented Start-up
P0317: No
Return
13:48
Select
Ready
0rpm
LOC
P0317
Oriented Start-up
[000] No
Return
13:48
Save
Ready
0rpm
LOC
P0317
Oriented Start-up
[001] Yes
Return
13:48
Save
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/f 60Hz
Reset
13:48
Select
e
Figure 10.2 - VVW mode Oriented Start-up
Seq.
Action/Result
- Set the content of P0202
pressing "Select".
- Next press
until
9
selecting the option "[005]
VVW", and then press
"Save".
- If necessary, change the
content of P0296 according
to the used line voltage.
Therefore press "Select".
This change will affect
10
P0151, P0153, P0185,
P0321, P0322, P0323 and
P0400.
- If necessary, change the
content of P0298 according
to the inverter application.
Therefore press "Select".
This change will affect
P0156, P0157, P0158,
11
P0401 and P0404. The
actuation time and level
of the IGBTs overload
protection will be affected.
- If necessary, change the
content of P0398 according
to the motor service factor.
Therefore press "Select".
This change will affect the
12
value of the current and the
time for the actuation of the
motor overload protection.
- If necessary, change the
content of P0399 according
to the rated motor
13
efficiency. Therefore press
"Select".
Display Indication
Config
0rpm
LOC
Language
P0201: English
Type of Control
P0202: V/f 60Hz
Reset
13:48
Select
Config
0rpm
LOC
P0202
Type of Control
[005] VVW
Return
13:48
Save
Config
0rpm
LOC
Type of Control
P0202: VVW
Line Rated Voltage
P0296: 440 - 460 V
Reset
13:48
Select
Config
0rpm
LOC
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Normal Duty
Reset
13:48
Select
Config
0rpm
LOC
Application
P0298: Normal Duty
Motor Service Factor
P0398:
1.15
Reset
13:48
Select
Config
LOC
0rpm
Motor Service Factor
P0398:
1.15
Motor Rated Eff.
P0399:
67.0 %
Reset
13:48
Select