Basic Filter Parameters; Setting The Forced Checking Procedure (Test Stop) - Siemens Sinamics G110M Operating Instructions Manual

Sinamics series distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Advanced commissioning
6.13 Safe Torque Off (STO) safety function
6.13.3.6

Basic filter parameters

Parameter
p9650
p9651
Debounce times for standard and safety functions
The debounce time p0724 for "standard" digital inputs has no influence on the fail-safe input
signals. Conversely, the same applies: The F-DI debounce time does not affect the signals
of the "standard" inputs.
If you use an input as a standard input, set the debounce time using parameter p0724 .
If you use an input as a fail-safe input, set the debounce time as described above.
6.13.3.7

Setting the forced checking procedure (test stop)

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
To set the forced checking procedure (test stop) of the basic functions, proceed as follows:
1. Select the screen form for setting the forced checking procedure.
2. Set the monitoring time to a value to match your application.
3. Using this signal, the inverter signals that a forced checking procedure (test stop) is
required.
Interconnect this signal with an inverter signal of your choice.
4. Close the screen form.
You have set the forced checking procedure (test stop) for the basic functions.
204
Description
F-DI changeover tolerance time (factory setting: 500 ms)
Tolerance time to change over the fail-safe digital input for the basic functions.
STO debounce time (factory setting: 1 ms)
Debounce time of the fail-safe digital input for the basic functions.
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 09/2017, FW V4.7.9, A5E31298649B AH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents