Appendix 2.6 Pc Link Communication Errors - Mitsubishi Electric Q172CPU Programming Manual

Motion controller, virtual mode.
Hide thumbs

Advertisement

APPENDICES

APPENDIX 2.6 PC link communication errors

Table 2.4 PC link communication error codes list
Error codes stored
in D9196
• A receiving packet for PC link
communication does not
arrive.
• The arrival timing of the
01
receiving packet is too late.
• A receiving packet CRC code
is not right.
02
• A receiving packet data ID is
not right.
03
• The number of received
frames is not right.
04
• A PC communication task
05
does not start.
Error description
APP - 36
Corrective action
• Check whether the power of PC has
been turned on.
• Check the connection of the
communication cable.
• Check the communication cable for
wire breakage.
• Check whether the A 0BD-PCF/
A30CD-PCF has been installed
correctly.
• Check whether there is a noise
source near the PC.
• Check the connection of the
communication cable.
• Check the communication cable for
wire breakage.
• Check whether the A 0BD-PCF/
A30CD-PCF has been installed
correctly.
• Replace the A 0BD-PCF/A30CD-
PCF.
• Check whether there is a noise
source near the PC.
• Check the connection of the
communication cable.
• Check the communication cable for
wire breakage.
• Start the communication task for PC
side.