1.6
CC-Link IE TSN Network Synchronous
Communication Function
This section describes the CC-Link IE TSN network synchronous communication function.
For details, refer to the following.
 MELSEC iQ-R Inter-Module Synchronization Function Reference Manual
For the firmware versions of the CPU module and RJ71GN11-T2 compatible with the CC-Link IE TSN network
synchronous communication function, refer to the following.
• CPU module ( MELSEC iQ-R CPU Module User's Manual (Application))
• RJ71GN11-T2 (Page 320 Added and Enhanced Functions)
Overview
This function synchronizes the control cycle of a slave station according to the inter-module synchronization cycle specified in
the master station via CC-Link IE TSN. This adjusts the operation timing with the operation timing of other slave stations
connected to the same network.
The following slave stations can be connected: slave stations not supporting the CC-Link IE TSN network
synchronous communication function and slave stations in which the network synchronous communication
setting is not set. However, they cannot synchronize with the inter-module synchronization cycle.
Master station
Inter-module synchronization
cycle for the master station
CPU module on the master station
Inter-module synchronous
interrupt program
Slave station No.1
Slave station No.2
Slave station No.3
1 FUNCTIONS
76

1.6 CC-Link IE TSN Network Synchronous Communication Function

Supporting Network
synchronous
communication function
Slave station No.1
Inter-module synchronization cycle
Input
Interrupt
Output
Input
Interrupt
refresh
program
refresh
refresh
program
Operate at the same timing of the
inter-module synchronization cycle
for the master station.
Supporting Network
synchronous
communication function
Slave station No.2
Output
Input
Interrupt
Output
refresh
refresh
program
refresh
Operate at the different timing of the
inter-module synchronization cycle
for the master station.
Not supporting Network
synchronous
communication function
Slave station No.3
Input
Interrupt
Output
refresh
program
refresh