Cc-Link Ie Field Network Synchronous Communication Function - Mitsubishi Electric NZ2GN2S1-16D User Manual

Cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

8.3
CC-Link IE Field Network Synchronous
Communication Function
I/O is performed with a synchronization cycle of the master station that supports the CC-Link IE Field Network synchronous
communication function.
This enables the I/O module to operate at the same timing as other slave stations on the same network.
The CC-Link IE Field Network synchronous communication function of the I/O module has the following two modes.
• Synchronous X/Y control mode ( Page 155 Synchronous X/Y control mode)
• Synchronization cycle timing control mode ( Page 157 Synchronization cycle timing control mode)
Applicable master module
When using the CC-Link IE Field Network synchronous communication function, use one of the following products as the
master module.
■MELSEC-Q/L series
Master module
QD77GF16
QD77GF8, QD77GF4
■MELSEC iQ-R series
Master module
RJ71GF11-T2
RJ71EN71
RnENCPU
RD77GF32, RD77GF16, RD77GF8, RD77GF4
To set the synchronization cycle in increments of 0.05ms, use one of the following products as the master module.
Master module
RJ71GF11-T2
RJ71EN71
RnENCPU
RD77GF32, RD77GF16, RD77GF8, RD77GF4
8 FUNCTIONS
154

8.3 CC-Link IE Field Network Synchronous Communication Function

Serial number (first five digits)
"17102" or later
"17101" or later
Firmware version
"01" or later
Firmware version
"03" or later
"01" or later

Advertisement

Table of Contents
loading

Table of Contents