KROHNE OPTIFLEX 8200 C Handbook page 96

Guided radar (tdr) level transmitter for liquids at high temperature and pressure
Hide thumbs Also See for OPTIFLEX 8200 C:
Table of Contents

Advertisement

OPERATION
6
Menu
Function
No.
2.5.8
Snapshot Mode
2.6.0 Communication
2.6.0 Communication
2.6.0 Communication
2.6.0 Communication
2.6.1
Polling Address
2.6.2
SV function
2.6.3
TV function
2.6.4
FV function
96
Function description
STATIC mode uses data from the quick
setup procedure in the Auto Setup
Auto Setup
Auto Setup
Auto Setup
procedure. This mode identifies and filters
interference signals from objects that do
not move in the tank. Snapshot function
data is saved if you de-energize the device.
CAUTION!
CAUTION!
CAUTION!
CAUTION!
Do not set this menu item to STATIC mode
before you do the quick setup procedure.
Any HART® address greater than 0 will
activate HART® multidrop mode. The
current output stays constant at 4 mA. If
2.6.1 Polling Address
2.6.1 Polling Address is set to 0, the device
2.6.1 Polling Address
2.6.1 Polling Address
will operate in point-to-point mode.
This is the second measurement type
shown on HART® controllers. Make a
selection from the list.
This is the third measurement type shown
on HART® controllers. Make a selection
from the list.
This is the fourth measurement type
shown on HART® controllers. Make a
selection from the list.
www.krohne.com
OPTIFLEX 8200 C/F/S
Selection list or range
of values
STATIC, DISABLE
min-max:
0...63
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
LEVEL, LEVEL
CONVERSION,
DISTANCE, DISTANCE
CONV., INTERFACE
LEVEL, INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER, LAYER
CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Default
DISABLE
0
DISTANCE
LEVEL