OPTIFLEX 8200 C/F/S
Menu
Function
No.
2.4.7
Output Function
I2
2.4.8
Output Range I2
2.4.9
Scale 4mA I2
2.4.10
Scale 20mA I2
2.4.11
Switch Function
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Function description
The output function for output 2. Make a
selection from a list of output functions to
scale the current values in relation to a
given point (usually the device process
connection or the tank bottom).
Conversion parameters (DISTANCE CONV.,
LEVEL CONVERSION etc.) are shown if
there is volume or mass data in menu item
1.2.0 Conversion Setup.
1.2.0 Conversion Setup
1.2.0 Conversion Setup
1.2.0 Conversion Setup
This function is available if menu item
2.4.6 Optional Output Mode is set to
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
"CURRENT".
This menu item sets the limits of the
output current range to 1 of the 2 available
options: standard limits (4...20 mA) or
NAMUR NE 43-compliant limits
(3.8...20.5 mA). It also tells the device what
to do if an error occurs. If you set 2.4.8
Output Range I2 to "4-20/22E" and an
Output Range I2
Output Range I2
Output Range I2
error occurs (e.g. the tank is too full etc.),
the device output current will change to an
error value of 22 mA. If you set 2.4.8
Output Range I2 to "4-20/HOLD" and the
Output Range I2
Output Range I2
Output Range I2
device senses a measurement error, the
value will stop at the last correct
measurement.
This function is available if menu item
2.4.6 Optional Output Mode is set to
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
"CURRENT".
This function gives a measurement value
to 4 mA (output 2).
This function is available if menu item
2.4.6 Optional Output Mode is set to
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
"CURRENT".
This function gives a measurement value
to 20 mA (output 2).
This function is available if menu item
2.4.6 Optional Output Mode is set to
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
"Current".
The switch function for output 2. Make a
selection from a list of switch functions to
set the switch signal to the function that
the device must monitor. For more data
about the switch function, refer to
output
on page 100.
This function is available if menu item
2.4.6 Optional Output Mode is set to
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
2.4.6 Optional Output Mode
"RELAY".
www.krohne.com
Selection list or range
of values
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
4-20/3.6E, 3.8-20.5/22E,
3.8-20.5/3.6E,
4-20/HOLD, 4-20/22E
2.4.8
2.4.8
2.4.8
2.4.8
2.4.8
2.4.8
min-max:
2
min-max:
2
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
Relay
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR
TEMPERATURE,
CURRENT mA,
CURRENT %,
ERROR LIST
OPERATION
Default
DISTANCE
4-20/3.6E
3
3
LEVEL
1
6
93