KROHNE OPTIFLEX 8200 C Handbook page 25

Guided radar (tdr) level transmitter for liquids at high temperature and pressure
Hide thumbs Also See for OPTIFLEX 8200 C:
Table of Contents

Advertisement

OPTIFLEX 8200 C/F/S
Figure 3-5: How to prevent build-up of product around the process connection
1 If product particles are likely to collect in holes, a nozzle is not recommended.
2 Attach the flange directly to the tank.
3 Use a threaded connection to attach the device directly to the tank.
For single cable and single rod probes:
Figure 3-6: Recommended nozzle dimensions for single rod and single cable probes
1 Recommended conditions: h ≤ d, where h is the height of the tank nozzle and d is the diameter of the tank nozzle.
2 The end of the nozzle must not have an extension into the tank. Do not install the device on a high nozzle.
CAUTION!
If the device is installed on a high nozzle, make sure that the probe does not touch the side of the
nozzle (attach the probe end etc.).
Figure 3-7: Sockets for threaded process connections
1 Recommended installation
2 The end of the socket must not have an extension into the tank
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
www.krohne.com
INSTALLATION
3
25