KROHNE OPTIFLEX 8200 C Handbook page 153

Guided radar (tdr) level transmitter for liquids at high temperature and pressure
Hide thumbs Also See for OPTIFLEX 8200 C:
Table of Contents

Advertisement

OPTIFLEX 8200 C/F/S
EAC-EX
(pending)
Other standards and approvals
Other standards and approvals
Other standards and approvals
Other standards and approvals
SIL (pending)
EMC
NAMUR
Conformity to construction codes
1 HART® is a registered trademark of the FieldComm Group™
2 If the device has a ceramic process seal system and a Kalrez® gasket, then T*= T1. For all other versions, T* = T3.
3 If the device has a ceramic process seal system and a Kalrez® gasket, then T*°C = T315°C. For all other versions, T*°C = T150°C.
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Compact version
Compact version
Compact version
Compact version
1Ex ia [ia Ga] IIC «T6...T*» Gb X;
Ex ia [ia Da] IIIC «T85°C...T*°C» Db
or...
1Ex db ia [ia Ga] IIC «T6...T*» Gb X;
Ex ia tb [ia Da] IIIC «T85°C...T*°C» Db*
Remote version, converter
Remote version, converter
Remote version, converter
Remote version, converter
1Ex ia [ia Ga] IIC «T6...T4» Gb X;
Ex ia [ia Da] IIIC «T85°C...T135°C» Db
or...
1Ex db ia [ia Ga] IIC «T6...T4» Gb X;
Ex ia tb [ia Da] IIIC «T85°C...T135°C» Db
Remote version, sensor
Remote version, sensor
Remote version, sensor
Remote version, sensor
1Ex ia [ia Ga] IIC «T6...T*» Gb X;
Ex ia [ia Da] IIIC «T85°C...T*°C» Db
C (Compact) and S (Sensor Extension) versions only: SIL 2/3 (SIL3: 1oo2
architecture is necessary for homogeneous redundancy)– certified according to all
the requirements in EN 61508 (Full Assessment) and for high/low continuous
demand mode operation. HFT=0, SFF=93% (for non-Ex / Ex i devices with one
output), 94% (for non-Ex / Ex i devices with two outputs) or 95% (for Ex d devices),
type B device
Electromagnetic Compatibility (EMC) directive. The device agrees with this directive
and its related standard if the device has a single probe that is installed in a metallic
tank.
Electromagnetic compatibility
For more data, refer to
SIL 2-approved devices agree with EN 61326-3-1 and EN 61326-3-2.
NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and
Laboratory Control Equipment
NAMUR NE 43 Standardization of the Signal Level for the Failure Information of
Digital Transmitters
NAMUR NE 53 Software and Hardware of Field Devices and Signal Processing
Devices with Digital Electronics
NAMUR NE 107 Self-Monitoring and Diagnosis of Field Devices
On request (for equipment used in the oil and gas industries):
NACE MR0175 (ISO 15156); NACE MR0103 (ISO 17945)
www.krohne.com
TECHNICAL DATA
2
3
2
3
2
3
on page 9.
8