NE 107
NE 107
symbol
Status
shown
Failure
Function
check
Out of
specification
Maintenance
1 CAUTION! The device display screen does not operate at this temperature
116
Description
The device does not operate
correctly. The fault message stays
on. The user cannot remove the
"Failure" message from the
Normal mode screen.
The device operates correctly, but
the measured value is incorrect.
This fault message is only
temporary. This symbol is shown
when the user configures the
device with the DTM or a HART®
Communicator.
It is possible that the measured
value is unstable if the operating
conditions do not agree with the
device specification.
The device does not operate
correctly because of bad
environmental conditions. The
measured value is correct, but
maintenance is necessary a short
time after this symbol is shown.
Status
Error code
marker
shown
1
101 (Error)
3
102 (Error)
1
103 (Error)
1
103 (Error)
1
103 (Error)
1
104 (Error)
2
200 (Error)
2
202 (Error)
3
203 (Error)
2
204 (Error)
3
205 (Error)
1
206 (Error)
1
207 (Error)
1
207 (Error)
1
207 (Error)
1
208 (Error)
3
209 (Error)
2, 4
210 (Error)
211 (Error)
4
214 (Error)
1
501 (Error)
4
(Warning)
4
(Warning)
4
(Warning)
4
(Warning)
5
(Warning)
4
(Warning)
4
(Warning)
4
(Warning)
3
(Warning)
3
(Warning)
6
(Warning)
www.krohne.com
OPTIFLEX 8200 C/F/S
Possible errors
(Type)
Current Output Drift
Temperature Out of Range
Converter EEPROM
Converter RAM
Converter ROM
Converter Voltage
Reference Lost
Peak Lost (Level Lost)
Sensor Processing Failure
Overfill
Internal Communication
No Probe detected
Sensor EEPROM
Sensor RAM
Sensor ROM
Oscillator Frequency
Sensor Not compatible
Empty
Sensor Hardware Failure
Interface Measurement
Failure
Optional Output Failure
Peak Lost
Overfill
Empty
Temperature out of range
Snapshot Invalid
Flange Lost
Reference Position Outside
Range
Audio Signal Offset Outside
Range
Temperature <-35°C /
-31°F
1
Temperature >+75°C /
+167°F
1
Probe End Analysis Not
Valid
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en