OPTIFLEX 8200 C/F/S
Menu
Function
No.
1.3.0 Device Setup
1.3.0 Device Setup
1.3.0 Device Setup
1.3.0 Device Setup
Use this quick setup procedure to give settings for output 1 and output 2
1.3.1
Output I1 Setup
Output Function
I1
Output Range I1
Scale 4mA I1
Scale 20mA I1
Output Error
Delay
Tag Name
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
Function description
Use this quick set-up procedure to give the settings for the current output of output 1.
These settings include the output function, output range, 4 mA setting, 20 mA setting,
output error delay and the tag name.
The output function for output 1. Make a
selection from a list of output functions to
scale the current values in relation to a
given point (usually the device process
connection or the tank bottom). The output
current value is shown on a bar graph in
normal mode if the measurement name
(displayed measurement) is the same as
the output function. Conversion
parameters (DISTANCE CONV., LEVEL
CONVERSION etc.) are shown if there is
volume or mass data in menu item 1.2.0
Conversion Setup.
Conversion Setup
Conversion Setup
Conversion Setup
This menu item sets the limits of the
output current range to 1 of the 2 available
options: standard limits (4...20 mA) or
NAMUR NE 43-compliant limits
(3.8...20.5 mA). It also tells the device what
to do if an error occurs. If you set Output
Range I1
Range I1
Range I1 to "4-20/22E" and an error
Range I1
occurs (e.g. the tank is too full etc.), the
device output current will change to an
error value of 22 mA. If you set Output
Range I1 to "4-20/HOLD" and the device
Range I1
Range I1
Range I1
senses a measurement error, the value
will stop at the last correct measurement.
This function gives a measurement value
to 4 mA (output 1).
This function gives a measurement value
to 20 mA (output 1).
The time after which the current output
changes to an error value. The error value
shows that there is a measurement error.
MN=minutes and S=seconds.
The device has a code (tag name) to
identify it. If the tag name is given in the
customer order data, it will be set at the
factory. A maximum of 8 characters can be
used.
www.krohne.com
Selection list or range
of values
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
1.2.0
1.2.0
1.2.0
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
4-20/3.6E, 3.8-20.5/22E,
3.8-20.5/3.6E,
4-20/HOLD, 4-20/22E
Output
Output
Output
Output
Output
Output
min-max:
2
min-max:
2
0 S, 10 S, 20 S, 30 S,
1 MN, 2 MN, 5 MN,15 MN
OPERATION
6
Default
LEVEL
4-20/3.6E
3
3
0 S
TANK 01