KROHNE OPTIFLEX 8200 C Handbook page 82

Guided radar (tdr) level transmitter for liquids at high temperature and pressure
Hide thumbs Also See for OPTIFLEX 8200 C:
Table of Contents

Advertisement

OPERATION
6
Menu
Function
No.
Switch Function
Set
Point/Threshold
Alarm Mode
Hysteresis
Error List
Process
analysis...
Probe analysis...
82
Function description
The switch function for output 2. Make
a selection from a list of switch
functions to set the switch signal to the
function that the device must monitor.
For more data about the switch
Relay output
function, refer to
100.
This function is available if Optional
Output Mode
Output Mode
Output Mode
Output Mode is set to "RELAY".
This function gives the point or
threshold (level, distance etc.) when
the device will send the relay signal.
This function is available if Optional
Output Mode is set to "RELAY" and
Output Mode
Output Mode
Output Mode
Switch Function is not set to "ERROR
Switch Function
Switch Function
Switch Function
LIST".
"LOW LEVEL ALARM" tells the device
to send the relay signal when the
quantity of product in the tank is less
than the threshold. "HIGH LEVEL
ALARM" tells the device to send the
relay signal when the quantity of
product in the tank is more than the
threshold.
This function is available if Optional
Output Mode
Output Mode is set to "RELAY" and
Output Mode
Output Mode
Switch Function is not set to "ERROR
Switch Function
Switch Function
Switch Function
LIST".
If Alarm Mode
Alarm Mode
Alarm Mode
Alarm Mode is set to "LOW LEVEL
ALARM", this gives the quantity of
product above the threshold where the
relay goes back to "off".
If Alarm Mode
Alarm Mode is set to "HIGH LEVEL
Alarm Mode
Alarm Mode
ALARM", this gives the quantity of
product below the threshold where the
relay goes back to "off".
This function is available if Optional
Output Mode
Output Mode is set to "RELAY" and
Output Mode
Output Mode
Switch Function
Switch Function
Switch Function
Switch Function is not set to "ERROR
LIST".
If Switch Function
Switch Function is set to "ERROR
Switch Function
Switch Function
LIST", Error List
Error List
Error List replaces the
Error List
Point/Threshold, Alarm Mode and
Hysteresis steps in this procedure.
This tells the device to send a relay
signal if the error condition specified in
this step occurs.
www.krohne.com
Selection list or range of
values
LEVEL, LEVEL CONVERSION,
DISTANCE, DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE CONVERSION,
INTERFACE DISTANCE,
on page
INTERFACE DIST. CONV.,
LAYER, LAYER CONVERSION,
DIELECTRIC PRODUCT,
Optional
DIELECTRIC GAS,
Optional
Optional
CONVERTER TEMPERATURE,
SENSOR TEMPERATURE,
CURRENT mA, CURRENT %,
ERROR LIST
min-max:
Optional
Optional
Optional
LOW LEVEL ALARM,
HIGH LEVEL ALARM
Optional
Optional
Optional
min-max:
Optional
Optional
Optional
OVERFILL, TANK EMPTY,
INTERFACE LOST,
CONV. TEMP. < MINI,
CONV. TEMP. > MAXI,
SNSR. TEMP. < MINI,
SNSR. TEMP. > MAXI,
DIELCT. CALC. FROZ.,
LEVEL LOST
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en