KROHNE OPTIFLEX 8200 C Handbook page 92

Guided radar (tdr) level transmitter for liquids at high temperature and pressure
Hide thumbs Also See for OPTIFLEX 8200 C:
Table of Contents

Advertisement

OPERATION
6
Menu
Function
No.
2.4.0 Outputs
2.4.0 Outputs
2.4.0 Outputs
2.4.0 Outputs
2.4.1
Output Function
I1
2.4.2
Output Range I1
2.4.3
Scale 4mA I1
2.4.4
Scale 20mA I1
2.4.5
Output Error
Delay
2.4.6
Optional Output
Mode
92
Function description
The output function for output 1. Make a
selection from a list of output functions to
scale the current values in relation to a
given point (usually the device process
connection or the tank bottom). The output
current value is shown on a bar graph in
normal mode if the measurement name
(displayed measurement) is the same as
the output function. Conversion
parameters (DISTANCE CONV., LEVEL
CONVERSION etc.) are shown if there is
volume or mass data in menu item 2.8.3
Input Table
Input Table
Input Table (Conversion Table).
Input Table
This menu item sets the limits of the
output current range to 1 of the 2 available
options: standard limits (4...20 mA) or
NAMUR NE 43-compliant limits
(3.8...20.5 mA). It also tells the device what
to do if an error occurs. If you set Output
Range I1
Range I1
Range I1 to "4-20/22E" and an error
Range I1
occurs (e.g. the tank is too full etc.), the
device output current will change to an
error value of 22 mA. If you set Output
Range I1 I to "4-20/HOLD" and the device
Range I1
Range I1
Range I1
senses a measurement error, the value
will stop at the last correct measurement.
This function gives a measurement value
to 4 mA (output 1).
This function gives a measurement value
to 20 mA (output 1).
The time after which the current output
changes to an error value. The error value
shows that there is a measurement error.
MN=minutes and S=seconds.
This function operates the optional second
output (output 2).
If you set this function to "CURRENT", the
second output supplies 4...20 mA. Give the
settings for this current output in 2.4.7
Output Function I2, 2.4.9 Scale 4mA I2
Output Function I2
2.4.9 Scale 4mA I2 and
Output Function I2
Output Function I2
2.4.9 Scale 4mA I2
2.4.9 Scale 4mA I2
2.4.10 Scale 20mA I2.
2.4.10 Scale 20mA I2
2.4.10 Scale 20mA I2
2.4.10 Scale 20mA I2
If you set this function to "RELAY", the
second output supplies a switch signal.
Give the settings for this relay signal in
2.4.11 Switch Function, 2.4.12 Set
2.4.11 Switch Function
2.4.12 Set
2.4.11 Switch Function
2.4.11 Switch Function
2.4.12 Set
2.4.12 Set
Point/Threshold
Point/Threshold
Point/Threshold
Point/Threshold, 2.4.13 Alarm Mode
2.4.13 Alarm Mode and
2.4.13 Alarm Mode
2.4.13 Alarm Mode
2.4.14 Hysteresis
2.4.14 Hysteresis. If 2.4.11 Switch Function
2.4.14 Hysteresis
2.4.14 Hysteresis
2.4.11 Switch Function
2.4.11 Switch Function
2.4.11 Switch Function
is set to "ERROR LIST", give the settings
for this relay signal in 2.4.12 Error List
2.4.12 Error List and
2.4.12 Error List
2.4.12 Error List
2.4.14 Delay
2.4.14 Delay
2.4.14 Delay
2.4.14 Delay.
www.krohne.com
Selection list or range
of values
LEVEL,
LEVEL CONVERSION,
DISTANCE,
DISTANCE CONV.,
INTERFACE LEVEL,
INTERFACE
CONVERSION,
INTERFACE DISTANCE,
INTERFACE DIST.
CONV., LAYER,
LAYER CONVERSION,
2.8.3
2.8.3
2.8.3
DIELECTRIC PRODUCT,
DIELECTRIC GAS,
CONVERTER
TEMPERATURE,
SENSOR TEMPERATURE
1
4-20/3.6E, 3.8-20.5/22E,
3.8-20.5/3.6E,
4-20/HOLD, 4-20/22E
Output
Output
Output
Output
Output
Output
min-max:
2
min-max:
2
0 S, 10 S, 20 S, 30 S,
1 MN, 2 MN, 5 MN,15 MN
DISABLE, CURRENT,
RELAY
4
2.4.7
2.4.7
2.4.7
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
OPTIFLEX 8200 C/F/S
Default
LEVEL
4-20/3.6E
3
3
0 S