OPTIFLEX 8200 C/F/S
Terminals for electrical installation (one current output / one switch output - relay)
Figure 4-12: Terminals for electrical installation (one current output / one switch output - relay)
1 Current output 1: Terminals
2 Switch power supply: Terminals
3 Switch output - relay: Terminals
4 Location of the external grounding terminal (on the wall support)
5 Grounding terminal in the housing (if the electrical cable is shielded)
CAUTION!
Use the applicable electrical cables with the cable glands.
Current outputs: Make sure that the current is not more than 4 A or that there is 4 A-rated
fuse in the electrical circuit that energizes the device.
Switch output - relay: Make sure that the current is not more than 5 A or that there is 5 A-
rated fuse in the electrical circuit that energizes the device.
Make sure that the polarity of the power supply is correct. If the polarity is incorrect, you will
not cause damage to the device but the device will not operate.
For more electrical installation data, refer to
06/2018 - 4006448901 - MA OPTIFLEX 8200 R01 en
ELECTRICAL CONNECTIONS
Compact version
www.krohne.com
on page 48.