Parameter Group 3-** Motor Start/Stop-2 - Danfoss VLT MCD 600 Operating Manual

Hide thumbs Also See for VLT MCD 600:
Table of Contents

Advertisement

Operating Guide | VLT® Soft Starter MCD 600
Option
Late Deceleration
Table 38: 2-12 - Adaptive Control Gain
Range
Function
* 75%
1–200%
Adjusts the performance of adaptive control. This setting affects both starting and stopping control.
Table 39: 2-13 - Multi Pump
Option
Function
Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a com-
mon outlet manifold.
*
Single Pump
Manifold Pump
Table 40: 2-14 - Start Delay
Range
* 0 s
0:00–60:00 (minutes:seconds)
Table 41: 2-15 - DC Brake Torque
Range
* 20%
20–100%
Table 42: 2-16 - DC Brake Time
Range
* 1 s
0:01–0:30 (minutes:seconds)
Table 43: 2-17- Brake Current Limit
Range
* 250%
100–600% FLC
Table 44: 2-18 - Soft Brake Delay
Range
*400 ms
400–2000
ms

10.7 Parameter Group 3-** Motor Start/Stop-2

The parameters in this group control the operation of the secondary configuration of the motor. Use the programmable input to select
the active motor set.
Danfoss A/S © 2018.10
Function
Function
Sets a delay after the soft starter receives a start command before it starts the motor.
Function
Sets the amount of brake torque the soft starter uses to slow the motor.
Function
Sets the duration for DC injection during a braking stop.
Function
Sets the time which the soft starter waits after a stop signal is received before it begins to supply braking
current to the motor. Set to allow time for K1 and K2 to switch.
Function
Sets the current limit for soft brake.
Programmable Parameters
AQ262141844215en-000202 / 175R1174 | 81