Download Print this page

Danfoss VLT LCP 601 Installation Manual

Remote control panel and mounting kit

Advertisement

Quick Links

Installation guide
Remote VLT® Control Panel LCP 601 and Mounting
Kit
VLT® Soft Starter MCD 600
1 Overview
1.1 Description
The remote VLT® Control Panel LCP 601 can be mounted up to 3 m (9.8 ft) away from the soft starter. The LCP is rated IP65 when
mounted correctly in accordance with these instructions.
The LCP connects to the soft starter via the DB9 connector on a hardware expansion card. A hardware expansion card must be installed
to use the remote LCP with the soft starter. Separate kits are available with a dedicated LCP connector expansion card, or with no
expansion card for applications already using another smart card.
1.2 Parts List
Item
Remote VLT® Control Panel LCP 601
LCP connector expansion card (selected kits)
Cable, DB9
Gasket, foam
Installation guide
M3 x 16 screw
M3 flat washer
M3 spring washer
M3 nut
Jack screw
Table 1: Ordering Numbers
Kit
Remote VLT® Cotrol Panel LCP 601 and Mounting Kit
Danfoss A/S © 2018.06
Quantity
1
1
1
1
1
4
4
4
4
4
Ordering number
175G0134
AN265232431650en-000101 / 175R1177 | 1

Advertisement

loading

Summary of Contents for Danfoss VLT LCP 601

  • Page 1 Installation guide M3 x 16 screw M3 flat washer M3 spring washer M3 nut Jack screw Table 1: Ordering Numbers Ordering number Remote VLT® Cotrol Panel LCP 601 and Mounting Kit 175G0134 Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177 | 1...
  • Page 2: Installation

    1. Push a small flat-bladed screwdriver into the slot in the center of the expansion port cover and ease the cover away from the soft starter. 2. Line up the card with the expansion port. Gently push the card along the guide rails until it clicks into the soft starter. 2 | Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177...
  • Page 3 2.3 Control via the Remote VLT® Control Panel LCP 601 The soft starter only accepts start and reset commands from the remote VLT® Control Panel LCP 601 if parameter 1A Command Source is set to Remote Keypad. Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177 | 3...
  • Page 4 Remote LCP N O T I C E If the commissioning menu is open on the built-in LCP, the soft starter ignores all commands from the remote LCP except stop commands. 4 | Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177...
  • Page 5: Mounting Diagram

    Drill 4 mounting holes for screws (1 in each corner) and 2 holes for the DB9 connector. N O T I C E The image is not to scale. Dimensions are given with the faceplate removed. Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177 | 5...
  • Page 6 Installation guide | Remote VLT® Control Panel LCP 601 and Installation Mounting Kit 68 mm (2.7 in) 62 mm (2.45 in) 13 mm (0.5 in) Illustration 2: Drilling Template 6 | Danfoss A/S © 2018.06 AN265232431650en-000101 / 175R1177...
  • Page 7 Installation guide | Remote VLT® Control Panel LCP 601 and Installation Mounting Kit 1 Faceplate 2 Screw 3 Jack screw 4 Flat washer 5 Spring washer 6 Nut 7 VLT® Control Panel LCP 601 8 Gasket 9 Panel 10 Cable Illustration 3: Exploded View...
  • Page 8 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.

This manual is also suitable for: