Operating Guide | VLT® Soft Starter MCD 600

5.5.4 Programmable Outputs

The programmable outputs (21, 22, 23 and 33, 34) can report the status of the soft starter or can control associated equipment.
The operation of the programmable outputs is controlled by parameters 8-1 to 8-6.

5.6 Control Voltage

5.6.1 Control Voltage Terminals

READY
RUN
TRIP
LOCAL
Exit
Menu
Reset
Store
VLT
®
Soft Starter
1/L1
3/L2
2/T1
4/T2
6/T3
Illustration 9:
Control Voltage Terminals
Connect the control supply according to the supply voltage being used.
MCD6-xxxxB-xx-CV2 (110–120 V AC): A8, A9.
MCD6-xxxxB-xx-CV2 (220–240 V AC): A7, A9.
MCD6-xxxxB-xx-CV1 (24 V AC/V DC): A8, A9.

5.6.2 UL Compliant Installation

For MCD6-0144B to MCD6-0579B to be UL-compliant, supplementary or branch circuit overcurrent protection must be used on the
control circuit supply (A7, A8, A9) in accordance with the electrical code applicable at the installation location.
32 | Danfoss A/S © 2018.10
5/L3
Installation
AQ262141844215en-000202 / 175R1174